|
Case History - Composite Cement Retainer
| Operator: |
Merit Energy |
| Well name: |
Pfeiffer 15-26 |
| Date run: |
March 20, 2007 |
| County: |
Weld |
| State: |
CO |
| Company Man |
Ron Singleton |
| Cell number: |
(970) 534-0031 |
| Well Type: |
Oil & Gas |
| Location: Sec |
26-T6N-R64W |
Well Parameters
| Casing: |
4-1/2”, 15.10# |
| Tubing workstring: |
2-7/8” EUE 8rd. |
| BHT: |
180 degrees F. |
Tool Specifications
| Composite Cement Retainer: |
4-1/2”, (10.50-15.10#), 8K, 250 F. |
| Outside diameter: |
3.60” |
| Length: |
32” |
| Running method: |
Wireline set |
| Wireline Running Speed: |
194 Ft. / minute |
| Setting depth: |
Setting depth: 3,504 Ft. |
Objective
Objective:
The operator wanted to squeeze the holes between 3,504 – 3,567 Ft. below the Composite Cement
Retainer, with the hope that the cement would come up around the outside of the pipe and re-enter the
casing through the holes between 3,413 – 3,444 Ft. Immediately following this squeeze, the operator
would sting out of the retainer, trip out of the hole, and then pump cement down the casing, followed by
a wiper plug to squeeze the holes between 3,351 – 3,383 Ft
Procedure:
- March 20, 2007 – 12:30 PM: The Composite Cement Retainer was run into the well, on wireline,
and set at 3,504 Ft. The Wireline running speed was 194 Ft / minute. The Cement Retainer Stinger
was tripped in on 2-7/8” tubing and landed at 1:30 PM. Shut down for the day.
- March 21, 2007 – 9:00 AM: The operator began pumping cement through the Composite Cement
Retainer maintaining 2,000 lbs of tubing weight on the retainer. At this point, the retainer had been
on depth, at temperature, for 19.5 hours. The maximum applied pressure was 70 psi. After squeezing
the bottom holes, the tubing was tripped out and cement was then pumped down the casing followed
by a wiper plug. The well was shut-in when the pressure on the plug reached 360psi.
- March 21, 2007 - 2:00 PM: The operator pressure tested the casing to 500 psi. No leaks. Tripped in
with a 3-5/8 Tri-cone bit and tagged the wiper plug 185 ft. above the Composite Cement Retainer.
- They drilled the cement down to the top of the Composite Cement Retainer and stopped to pressure
test the casing to 600 psi. No leaks. Drilled through the 185 ft. of cement averaging 30 minutes per
joint while reverse circulating.
- Resumed drilling on the top of the Composite Cement Retainer. It took 1 hour to drill down through
the bottom set of slips to the top of the aluminum-sliding sleeve valve housing, approximately 21-
1/4”. At this point the bit quit drilling. Tripped the bit. The center rows of teeth on the each of the 3
cones of the Tri-cone bit were worn off. Tripped in with a new Tri-cone bit and finished drilling the
valve assembly housing, approximately 11-3/4”, in 60 minutes. Total drilling time was 2 hours.
Conclusion:
- The Composite Cement Retainer performed flawlessly, in spite of the fact that the retainer sat on
depth at 180 degrees F for 19-1/2 hours before cementing operations began. The manufacturer
recommends that the retainer be set and cementing operations are completed all in the same day. So,
this was a good test of the durability of the composite material.
- The sliding sleeve valve performed as expected. The valve opened and closed and held pressure as
designed.
- The only downside was the operator’s choice of the type of bit to drill up the cement and the
retainer. A Tungston Carbide Drag bit, Hurricane mill, or Chomp mill would have been a better
choice, both in terms of durability and faster drill times. Based on field experience, the Composite
Cement Retainer should have drilled up in 1 to 1-1/2 hours with either of these alternative bit
choices.
This field test was witnessed by:
Gary McKelvey
Graco Corporate Sales
Cell: 303-550-8179
|